DSCA190V 57310001-PK數字量模塊的產生
所有與轉換器直接連接的電力電纜(U1、V1、W1、C1、D1)必須被屏蔽或保持在一起,靠近安裝板,并與其他所有部件分開電纜(包括L1、L2、L3),尤其是來自未屏蔽信號的電纜電纜。建議的分離可能性是放置這些安裝板后側的電源電纜。如果“污染”電纜和其他電纜,特別是信號電纜的直接交叉
不可避免的是,它們必須是矩形的。16.放置室外電纜
內閣電力電纜必須平行且緊密地布置在一起,參見14中的圖紙。必須篩選速度反饋,并且直接沿電機的電源電纜放置,如果外殼轉速表電機的外殼與馬達。如果轉速表或編碼器外殼與電機絕緣,則電源和信號之間的距離電纜是有利的。
歐洲公共低壓線路的額定電壓為400 V
三相之間以及a相和中性點之間的230 V
導體這些電壓由變壓器及其3提供-星形連接的相二次繞組。星形點與中性導線連接,并在變電站接地。電力由4線電纜分配給電力消費者。在消費者的電纜接頭處
中性導線必須接地(房屋的局部接地或然后將其分為中性線和PE導體。
因此,必須提供帶有中性導線的三相負載
通過5線電纜。然而,轉換器是三相負載,其大多數情況下不需要中性導線。他們可以如圖5.2-1所示,由4線電纜供電
從房屋、工廠外的接地中性導線或工廠至內部PE導線和本地接地點
圖中未顯示中間。另見第24節。
功率限制:見第4節末尾!
工業區19條公共低壓線路
在工業區,由轉換器引起的噪聲水平允許比包括輕工業的住宅區高10dB。因此,保護目標涉及:如果這些電纜符合以下要求,則無需屏蔽電機電纜即可滿足EMC要求:根據14配置。
工業區的公共低壓線路可能有自己的線路
供電變壓器如圖5.2-1所示,但通常工業區和住宅區由普通變壓器。這取決于的功耗
兩個區域及其距離。功率限制:見第4條末尾!
All power cables which are directly connected with the converter
(U1, V1, W1, C1, D1) must either be screened or be kept close together and close to the mounting plate and separate from all other
cables (L1, L2, L3 included) and especially from unscreened signal
cables. A recommended separation possibility is to place these
power cables at the rear side of the mounting plate. If direct crossings of "polluted" cables and others, especially signal cables, are
inevitable then they must be made rectangular.
16 Placement of
cables outside
the cabinet
The power cables must be arranged parallel and close together,
see drawings in 14. The speed feedback must be screened and
placed directly along the power cables to the motor if the housing
of the tacho machine is electrically connected with the housing of
the motor. If the housing of the tachometer or the encoder is insulated from the motor then a distance between the power and signal
cables is advantageous.The rated voltages of a public European low voltage line are 400 V
between the 3 phases and 230 V between a phase and the neutral
conductor. These voltages are provided by a transformer with its 3-
phase secondary winding in star connection. The star point is connected with the neutral conductor and it is earthed at the transformer station. The electrical power is distributed by 4-wire cables
to the electricity consumers. At a cable stub to a consumer, the
neutral conductor must be earthed (local earth of the house or
plant), and then it is split into a neutral and a PE conductor.
Therefore a 3-phase load with neutral conductor must be supplied
by a 5-wire cable. Converters, however, are 3-phase loads which
do not need the neutral conductor in most cases. They can be
supplied by 4-wire cables as shown in figure 5.2-1. The change
from the earthed neutral conductor outside the house, plant or
factory to the internal PE conductor with the local earthing point
between is not shown in this figure. See also section 24.
Power limitation: see end of section 4!
19 Public low voltage lines in industrial regions
In an industrial region the noise level which is caused by converters
is allowed to be 10 dB higher than in a residential region with included light industry. Therefore the protection targets concerning
EMC can be met without screened motor cables if these cables are
configured according to 14.
A public low voltage line of an industrial region may have an own
supply transformer as shown in figure 5.2-1, but often the lines of
an industrial region and of a residential one are supplied by a
common transformer. This depends on the power consumption of
both regions and on their distance. Power limitation: see end of 4!