在同一控制網絡內重復使用從冗余配置中更換的CPU模塊可能會由于MAC和IP地址處理而導致控制網絡問題。參見第49頁冗余配置中的MAC和IP地址處理。除非已知被替換的模塊和先前與其一起在冗余配置中工作的模塊從先前的相互地址交換中恢復,否則不應實現這種重用。建議設置IP配置會話,然后使用“恢復出廠設置”選項,然后重新分配IP地址或分配新的IP地址。使用BC810進行配置時,不要在5.0之前的版本中在線更換RCU鏈接電纜。支持在線更換還取決于硬件產品版本級別。有關詳細信息,請參閱發行說明(3BSE021377*)。如果證明支持在線更改,在考慮了上述警告后,BC810外部提供24V電源,則可以遵循與不帶BC810的配置相同的步驟。
Reuse of CPU modules replaced from redundant configurations within the same control network, might cause control network problems due to the MAC and IP address handling. See MAC and IP Address Handling in Redundant Configuration on page 49. Such reuse should not be fulfilled unless both the replaced module and the module previously acting together with it in redundant configuration are known to be restored from the previous mutual address swap. It is recommended to set up an IP-config session and use the “Restore factory settings” option subsequently followed by reassignment of the IP address or assignment of a new IP address.In Configuration with BC810 Do not replace the RCU link cable online in a previous version than 5.0. The support for online replacement also depends on hardware Product Revision levels. Please consult Release Notes (3BSE021377*) for detailed information.If online change proves to be supported, after the caution above has been considered, and the BC810s are externally supplied with 24V the same steps as in configuration without BC810 can be followed.