BENTLY 3500/20 125768-01數據輸入模塊
BENTLY 3500/20 125768-01數據輸入模塊中文資料:
BENTLY 3500/20 125768-01數據輸入模塊模擬輸出模塊接線概述每個輸出應使用質量良好的屏蔽線連接,電纜屏蔽在模塊端接地。有關更多信息,請參閱GFK-0898,Series 90-30 PLC I/O Module Specification(GFK-088系列90-30 PLC輸入/輸出模塊規格)。使用通用接線板或接線板將接線板安裝在控制外殼內,并將屏蔽電纜從接線板連接到模塊接線板端子上的每個輸出電路。?僅在模塊端將每條電纜的屏蔽接地。不要在端子排末端連接屏蔽(在電纜的端子排末端切斷屏蔽并用熱縮管絕緣)。?用屏蔽電纜將現場設備連接到端子板,僅在端子板端部將屏蔽接地(在電纜的現場設備端部切斷屏蔽并用熱縮管絕緣)BENTLY 3500/20 125768-01。此外,應盡可能縮短端子板和設備端的外露(屏蔽外部)引線的長度。直接方法?將屏蔽電纜從每個現場設備(傳感器、電位計等)直接連接到模塊。?將導體連接到模塊端子板上的適用螺釘。?僅在模塊端將屏蔽接地,使最小數量的導體暴露在噪聲環境中。不要在設備端連接屏蔽(切斷電纜設備端的屏蔽,并用熱縮管進行絕緣)。BENTLY 3500/20 125768-01
英文資料
Analog Output Module Wiring General Each output should be connected using a good quality shielded wire with the cable shield grounded at the module end. See GFK-0898, Series 90-30 PLC I/O Module Specifications, for more information. Using a Generic Terminal Block or Strip ? Mount a terminal strip inside the control enclosure and run a shielded cable from the terminal strip to each output circuit on the module’s terminal board terminals. ? Ground each cable’s shield at the module end only. Do not connect the shields at the terminal strip end (cut shields off at terminal strip end of cables and insulate with shrink tubing). ? Wire the field device to the terminal strip with shielded cables, grounding the shields at the terminal strip end only (cut shields off at field device end of cables and insulate with shrink tubing). Also, keep the length of exposed (outside of shield) leads at the terminal strip and device ends as short as possible. Direct Method ? Run a shielded cable from each field device (transducer, potentiometer, etc.) directly to the module. ? Connect the conductors to the applicable screws on the module’s terminal board. ? Ground the shield at the module end only, exposing a minimum amount of conductor to the noisy environment. Do not connect the shield at the device end (cut shield off at device end of cable and insulate with shrink tubing).BENTLY 3500/20 125768-01
每 日 展 示
公 司 主 營 優 勢
應 用 行 業