隔離板
RGU隔離板表A:負(fù)載電阻器套件J7 1 J2 1 TB4 1 TB6 1 TB5 1 J1 1 P1 SW1 115V TB31 TB21 TB31*注:TB2僅用于B系列RGU(或RGU至交流線路至直流母線至主控制板(J12)至未使用的電流傳感器T相負(fù)載電阻器(F17、F18、F19)S相負(fù)載電阻器*R相負(fù)載電阻器至控制電路電路由于銘牌顯示這是一個(gè)a系列裝置,TB2中不需要電阻器。a系列B出版物2364F-5.13 1999年6月RGU? 隔離板更換5安裝隔離板1.將負(fù)載電阻器固定在新板上的端子中(驗(yàn)證透明絕緣層沒有進(jìn)入端子)。擰緊至6 lb in(0.7 N-m)。注:TB2僅用于B系列RGU(見數(shù)據(jù)銘牌)。
固定電路板
將電路板放在六個(gè)支架上并固定電路板。3.將端子塊TB5和TB6連接至隔離板。接線板必須牢固地壓入適當(dāng)?shù)牟遄小?.將反饋連接連接到J1,將帶狀電纜連接到J2,將電流傳感器連接到J7,將PE地線連接到P1。5.將Lexan防護(hù)罩更換到隔離板上。6.驗(yàn)證SW1設(shè)置正確(115V AC)。結(jié)束步驟安裝隔離板后,更換所有Lexan屏蔽并固定隔間門。將電路板送至自動(dòng)化公司進(jìn)行維修,或根據(jù)貴公司的程序和當(dāng)?shù)貤l例處理舊電路板!注意:SW1必須設(shè)置為適當(dāng)?shù)目刂乒β省W1設(shè)置為錯(cuò)誤設(shè)置將導(dǎo)致隔離板和其他部件損壞。出版物2364F-5.13 1999年6月PN 192666取代出版物2364F-5.13 1999 1999年3月版權(quán)所有1999年國際公司。美國印刷Lexan是通用電氣公司的商標(biāo)
Isolation plate
RGU isolation board table A: load resistor kit J7 1 J2 1 TB4 1 TB6 1 TB5 1 J1 1 P1 SW1 115V TB31 TB21 TB31 * Note: TB2 is only used for B series RGU (or RGU to AC line to DC bus to main control board (J12) to unused current sensor T phase load resistor (F17, F18, F19) S phase load resistor * R phase load resistor to control circuit circuit Since the nameplate shows that this is a series device, no resistor is required in TB2. A Series B Publication 2364F-5.13 June 1999 RGU ? Replace the isolation board 5 Install the isolation board 1. Fix the load resistor in the terminal on the new board (verify that the transparent insulating layer does not enter the terminal). Tighten to 6 lb in (0.7 N-m). Note: TB2 is only used for B series RGUs (see data nameplate).
Fixed circuit board
Place the circuit board on the six brackets and secure the circuit board. 3. Connect terminal blocks TB5 and TB6 to the isolation board. The terminal block must be firmly pressed into the appropriate socket. 4. Connect the feedback connection to J1, the ribbon cable to J2, the current sensor to J7, and the PE ground wire to P1. 5. Replace the Lexan shield onto the isolation plate. 6. Verify that SW1 is set correctly (115V AC). At the end of the step, replace all Lexan shields and secure the compartment door after installing the isolation panel. Send the circuit board to the automation company for maintenance, or dispose of the old circuit board according to your company's procedures and local regulations! Note: SW1 must be set to the appropriate control power. Setting SW1 to the wrong setting will cause damage to the isolation panel and other components. Publication 2364F-5.13 June 1999 PN 192666 replaces publication 2364F-5.13 March 1999 Copyright 1999 International Corporation. Printed in the United States Lexan is a trademark of General Electric Company