DS200TCEAG1BRE模擬量輸出模塊
模擬輸出
–CC-PAOX01功能模擬輸出(AO)模塊向致動器和記錄/指示裝置提供高電平恒定電流。值得注意的功能?廣泛的自我診斷?可選冗余?每個通道可配置的安全狀態(FAILOPT)行為?輸出回讀和差異報警?非易燃輸出FAILOPC系列AO模塊支持每個通道的FAILOPD參數。用戶可以將每個通道配置為保持最后一個值或設置為安全值。如果IOM設備電子設備發生故障,輸出將始終歸零,即安全狀態。
開路檢測此C系列
IO功能將能夠檢測并通過通道軟故障指示通知開路現場線。詳細規范–高級模擬輸出參數規范輸入/輸出型號CC-PAOX01-高級模擬輸出IOTA型號CC-TAOX01非冗余6“CC-TAOX11冗余12”CC-GAOX11非冗余12“CC-GAOX21非冗余6”輸出類型4-20 mA輸出通道16輸出紋波<100 mV,參數規格輸入/輸出型號CC-PDOD51-24V數字輸出,現場隔離,總線輸出,涂層IOTA型號CC-TDOD51非冗余9“CC-TDOD161冗余12”輸出通道32輸出類型SINK(開路漏極)負載電壓15 30 VDC最大負載電流0.1 A/通道(最大)電流隔離1000 VAC RMS用于系統到現場隔離(用戶提供的現場電源)開態電壓0v VDC(負載電流@0.1A最大)關態電壓24 V(典型值),關斷狀態泄漏電流100μA(最大)開啟/關閉時間10 ms(最大)輸出到現場的間隙(0電流)無(0ms)(僅適用于冗余)Experion系列C輸入/輸出規范,EP03-490-520 39版本1.5霍尼韋爾專有2021 12月5.19。
Analog Output
– CC-PAOX01 functional analog output (AO) module provides high level constant current to actuator and recording/indicating device. Notable functions ? Extensive self diagnosis ? Optional redundancy ? Configurable safe state (FAILOPT) behavior for each channel ? Output readback and differential alarm ? Non incendive output FAILOPC series AO modules support FAILOPD parameters for each channel. You can configure each channel to hold the last value or set it as a safe value. If the electronic device of the IOM device fails, the output will always return to zero, that is, the safe state.
Open circuit detection of this C series
The IO function will be able to detect and notify open field lines through channel soft fault indication. Detailed specification – Advanced analog output parameter specification Input/output model CC-PAOX01 Advanced analog output IOTA model CC-TAOX01 Non redundant 6 "CC-TAOX11 redundant 12" CC-GAOX11 non redundant 12 "CC-GAOX21 non redundant 6" output type 4-20 mA output channel 16 output ripple<100 mV, parameter specification Input/output model CC-PDOD51-24V digital output, field isolation, bus output, Coating IOTA model CC-TDOD51 non redundant 9 "CC-TDOD161 redundant 12" output channel 32 output type SINK (open drain) load voltage 15 30 VDC maximum load current 0.1 A/channel (maximum) current isolation 1000 VAC RMS for system to site isolation (user provided site power supply) open state voltage 0v VDC (load current @ 0.1A maximum) closed state voltage 24 V (typical), Off state leakage current 100 μ A (maximum), opening/closing time 10 ms (maximum), gap output to the site (0 current), no (0 ms) (only applicable to redundancy), Experion Series C input/output specification, EP03-490-520, 39 version 1.5, Honeywell proprietary, December 5.19, 2021.