DS200TCQBG1BBA控制系統
在電源線頻率
下峰值到峰值,跨越250? 負載輸出溫度漂移0.005%滿量程/°C輸出回讀精度±4%滿量程輸出電流線性度±0.05%滿量程標稱分辨率±0.05%全量程校準精度±0.35%滿量程(25oC),包括線性度直接設定輸出電流范圍0 mA,2.9 mA至21.1 mA最大電阻負載(24 V電源=22 VDC至28 VDC)800歐姆最大輸出兼容電壓(24 V供電=22 VDC到28 VDC)16 V Experion Series-C I/O規范,EP03-490-520 26版本1.5霍尼韋爾專有2021 12月參數規范最大開路電壓22 V響應時間(DAC輸入代碼到輸出)在最大10毫秒(僅適用于冗余)切換時輸出到現場的80毫秒間隙(0 mA)內沉降到最終值的1%以內Experion Series-C輸入/輸出規范,EP03-49 0-520 27版本1.5Honeywell專有2021 12月5.11日。
功能模擬輸出
擬輸出–CC-PAON01功能模擬輸出(AO)模塊向致動器和記錄/指示裝置提供高電平恒定電流。值得注意的功能?廣泛的自我診斷?可選冗余?每個通道可配置的安全狀態(FAILOPT)行為?輸出回讀和差異報警?非易燃輸出FAILOPC系列AO模塊支持每個通道的FAILOPD參數。用戶可以將每個通道配置為保持最后一個值或設置為安全值。如果IOM設備電子設備發生故障,輸出將始終歸零,即安全狀態。開路檢測此C系列IO功能將能夠通過通道軟故障指示來檢測和通知開路現場線詳細規范-高級模擬輸出參數規范輸入/輸出型號CC-PAON01-高級模擬輸入IOTA型號CC-TAON01非冗余6“CC-TAON 11冗余12”輸出類型4-20 mA輸出通道16輸出紋波<100電源線頻率下的峰間電壓為mV
At power line frequency
Lower peak value to peak value, across 250 Ω load Output temperature drift 0.005% Full scale/° C Output back reading accuracy ± 4% Full scale output current linearity ± 0.05% Full scale nominal resolution ± 0.05% Full scale calibration accuracy ± 0.35% Full scale (25oC), including linearity Direct setting output current range 0 mA, 2.9 mA to 21.1 mA maximum resistive load (24 V power supply=22 VDC to 28 VDC) 800 ohms maximum output compatible voltage (24 V power supply=22 VDC to 28 VDC) 16 V Experion Series-C I/O specification, EP03-490-520 26 version 1.5 Honeywell proprietary 2021 December parameter specification The maximum open circuit voltage 22 V response time (DAC input code to output) settles to within 1% of the final value within the 80 millisecond gap (0 mA) when the output is switched to the site in the maximum 10 milliseconds (only applicable to redundancy) Experience Series-C input/output specification, EP03-49 0-520 27 version 1.5 Honeywell proprietary 2021 December 5.11.
Function analog output
Intended Output – The CC-PAON01 functional analog output (AO) module provides a high level constant current to the actuator and the recording/indicating device. Notable functions ? Extensive self diagnosis ? Optional redundancy ? Configurable safe state (FAILOPT) behavior for each channel ? Output readback and differential alarm ? Non incendive output FAILOPC series AO modules support FAILOPD parameters for each channel. You can configure each channel to hold the last value or set it as a safe value. If the electronic device of the IOM device fails, the output will always return to zero, that is, the safe state. Open circuit detection This C series IO function will be able to detect and notify the open circuit field line detailed specification - advanced analog output parameter specification Input/output model CC-PAON01 - advanced analog input IOTA model CC-TAON01 non redundant 6 "CC-TAON 11 redundant 12" output type 4-20 mA output channel 16 Output ripple<100 Peak to peak voltage at power line frequency is mV