330105-02-12-05-02-00前置傳感器
注意事項
如果模塊OK(正常)狀態變為not OK(不正常),則機架接口輸入/輸出模塊上的系統OK繼電器將被驅動為not OK(異常)。Configuration Fault(配置故障)表示機架接口模塊配置是否無效。通道狀態正常這表示是否在通道或模塊內檢測到故障。如果通道OK狀態變為not OK,則機架接口輸入/輸出模塊上的系統OK繼電器將被驅動為not OK。下表顯示了可找到狀態的位置。狀態通信網關模塊機架配置軟件操作員顯示軟件模塊OK X X模塊配置故障X通道OK X X 3500/20操作和維護2一般信息5 2.3 LED說明機架接口模塊前面板上的LED指示模塊的運行狀態,如下圖所示。有關所有可用的LED條件,請參閱第6.2節。1) OK(正常):表示機架接口模塊和I/O模塊工作正常。2) TX/RX:以發送消息的速率閃爍。3) TM:指示機架是否處于跳閘倍增模式。4) Config OK(配置正常):表示機架中的任何模塊未配置或存在配置錯誤,或機架接口模塊的存儲配置與機架3配置信息3500/20操作和維護6 3配置信息的物理配置不匹配本節描述了如何使用機架配置配置機架接口模塊軟件它還描述了與此模塊相關的任何配置注意事項。
有關如何操作
軟件的詳細信息,請參閱3500監測系統機架配置和實用程序指南和機架配置軟件。3.1軟件配置選項本節顯示了與機架接口模塊相關的機架配置軟件的配置屏幕,并討論了配置注意事項。它將顯示軟件屏幕的副本,并解釋可用的選項。3.1.1機架接口模塊配置注意事項機架接口模塊選項屏幕上指定的后端口I/O選項和電源選項必須與系統的物理組件匹配。如果發現配置不匹配,機架將不接受下載的配置3.1.2機架接口模塊配置本節描述了機架接口模塊組態屏幕上的可用選項。
matters needing attention
If the module OK status changes to not OK, the system OK relay on the Rack Interface I/O Module will be driven to not OK. Configuration Fault indicates whether the Configuration of the Rack Interface Module is invalid. Channel status OK This indicates whether a fault has been detected in the channel or module. If the channel OK status changes to not OK, the system OK relay on the Rack Interface I/O Module will be driven to not OK. The following table shows where the status can be found. Status Communication Gateway Module Rack Configuration Software The operator displays the software module OK X X Module Configuration Fault X Channel OK X X 3500/20 Operation and Maintenance 2 General Information 5 2.3 LED that indicate the operating status of the module on the front panel of the Rack Interface Module, as shown in the following figure. Refer to Section 6.2 for all available LED conditions. 1) OK: Indicates that the Rack Interface Module and I/O Module are working properly. 2) TX/RX: Flashes at the rate at which messages are sent. 3) TM: Indicates whether the rack is in Trip Multiply mode. 4) Config OK: indicates that any module in the rack is not configured or has a configuration error, or the storage configuration of the Rack Interface Module does not match the physical configuration of the 3500/20 operation and maintenance 6 3 configuration information. This section describes how to use the Rack Configuration to configure the Rack Interface Module software. It also describes any configuration considerations related to this module.
About how to
For software details, refer to the 3500 Monitoring System Rack Configuration and Utilities Guide and Rack Configuration Software. 3.1 Software Configuration Options This section displays the configuration screen for the Rack Configuration Software associated with the Rack Interface Module and discusses configuration considerations. It displays a copy of the software screen and explains the available options. 3.1.1 Rack Interface Module Configuration Considerations The rear port I/O options and power options specified on the Rack Interface Module Options screen must match the physical components of the system. If a configuration mismatch is found, the rack will not accept the downloaded configuration3.1.2 Rack Interface Module ConfigurationThis section describes the options available on the Rack Interface Module Configuration screen.