KOKUSAI BALEXT-SMP 1數控采集卡件
在最后一個通道E/A7(輸入/輸出7)掃描,再次按下測試按鈕會導致指示燈亮起要執行的測試(LED測試)。所有8個LED都應亮起向上的松開按鈕后,LED將顯示插件底座上DIL開關的設置約5秒。LED 0顯示開關的位置1號(LED 0…7分配給1…8號交換機)。
所有錯誤消息都存儲在模塊中,并且只能按下測試按鈕10秒刪除,或通過電源關閉/打開診斷A4.1簡介07 KR 91/07 KT 92的診斷系統/07 KT 93旨在確保快速高效故障排除。為此,分類如下:診斷中的“垂直”、錯誤標志、反應、LED顯示和確認,見第A4.7章。總線主機之間存在相互關系
中央單元和遠程模塊。中央單元讀取遠程模塊的診斷數據已經發現了。中央致謝單元還會導致存儲在要刪除的遠程模塊。
4個錯誤類別中的“水平”,對應錯誤的嚴重程度,見第A4.7章。這個概念基于一個系統結構,包括一個總線主中央單元和幾個遠程模塊,以及遠程處理器。診斷系統
檢測以下錯誤:總線主中央單元錯誤
CS31系統總線上的錯誤
遠程模塊中的錯誤上遠程模塊的接線錯誤工藝方面故障排除如下:中央單元07 KR 91、07 KT 92和07 KT 93給出初步提示,見第A4.3章。錯誤還顯示遠程模塊檢測到的在這里如果這些提示不夠,錯誤標志必須被讀出。有關錯誤標志的含義,請參閱第A4.7和A4.10章。
中央單元中的狀態寄存器EW 07,15提供了用于診斷,參見第A4.9章。
遠程模塊指示其地區詳細信息可通過以下方式獲得按下模塊上的測試鍵,參見第章A4.4、。After the last channel E/A7 (input/output 7) has been
scanned, pressing the test button again causes a lamp
test (LED test) to be performed. All the 8 LEDs should light
up. After the button has been released, the LEDs will
show the setting of the DIL switch on the plug-in base for
approx. 5 seconds. LED 0 shows the position of switch
No. 1 (LEDs 0...7 are assigned to the switches No. 1...8).
All error messages are stored in the module and can only
be deleted by pressing the test button for 10 seconds or
by power OFF/ON.Diagnosis
A4.1 Introduction
The diagnosis system of the 07 KR 91 / 07 KT 92 /
07 KT 93 is designed to ensure a quick and efficient
troubleshooting. For this purpose, it is classified:
”vertically” in diagnosis, error flags, reactions, LED
displays and acknowledgement, see chapter A4.7.
There are interrelations between the bus master
central unit and the remote modules. The central unit
reads the diagnosis data which the remote modules
have found out. An acknowledgement in the central
unit also causes the stored error messages in the
remote modules to be deleted.
”horizontally” in 4 error classes, in correspondence
with the severity of the error, see chapter A4.7.
This concept is based on a system structure consisting of
a bus master central unit and several remote modules,
and remote processors as well. The diagnosis system
detects the following errors:
Errors in the bus master central unit
Errors on the CS31 system bus
Errors in the remote modules
Errors in the wiring of the remote modules on the
process side
The troubleshooting is performed as follows:
The LEDs on the central unit 07 KR 91, 07 KT 92 and
07 KT 93 give first hints, see chapter A4.3. The errors
detected by the remote modules are also displayed
here.
If these hints are not sufficient, the error flags have to
be read out. For the meaning of the error flags, see
chapters A4.7 and A4.10.
The status register EW 07,15 in the central unit
supplies additional information to be used for the
diagnosis, see chapter A4.9.
The remote modules indicate errors occurring in their
area. Detailed information can be obtained by
pressing the test key on the modules, see chapter
A4.4.