IS210AEBIH3BEC燃機(jī)電氣模塊
無功功率階躍響應(yīng)-VAR設(shè)定值的減少(%)。該字段表示減少單擊相應(yīng)的減量按鈕時,F(xiàn)CR設(shè)定點(diǎn)發(fā)生。“減少VARSetpoint=“字段用于設(shè)置和指示當(dāng)單擊減量按鈕。范圍內(nèi)或更低的任何設(shè)定點(diǎn)值(表示為標(biāo)稱值的百分比)可以在“減少VAR設(shè)定值”字段中輸入現(xiàn)有設(shè)定值。var設(shè)定點(diǎn)單擊相鄰按鈕時更改為新值。點(diǎn)擊該按鈕發(fā)送var設(shè)定值值設(shè)置為DECS-100,并將按鈕的顏色從灰色更改為紅色。
無功功率階躍響應(yīng)-儀表值。這些字段和撥號指針指示選擇的var設(shè)定點(diǎn)。當(dāng)通過單擊增量、減量或設(shè)定點(diǎn)更改var設(shè)定點(diǎn)時按鈕,儀表值字段和刻度盤指針指示設(shè)定值。新的var設(shè)定點(diǎn),表示為作為kvar值或標(biāo)稱百分比,可直接輸入儀表值字段或選擇通過將撥號指針拖動到所需值。新值通過單擊發(fā)送到DECS-100發(fā)送按鈕。
無功功率階躍響應(yīng)-電流設(shè)定點(diǎn)(%)。有功var設(shè)定值(通過使用以下任一項(xiàng)進(jìn)行調(diào)整:前面提到的方法)顯示在該字段中。將var設(shè)定值返回至標(biāo)稱值設(shè)置時,應(yīng)點(diǎn)擊“VAR設(shè)定點(diǎn)(%)(標(biāo)稱)”字段旁邊的按鈕。如果VAR選項(xiàng)卡為左鍵可查看其他選項(xiàng)卡或屏幕,無需將VAR設(shè)定點(diǎn)返回至標(biāo)稱值,VAR設(shè)定值對話框出現(xiàn)。單擊“是”按鈕將var設(shè)定值返回至標(biāo)稱值。單擊“否”將維護(hù)var當(dāng)前值的設(shè)定點(diǎn)。
保護(hù)設(shè)置
保護(hù)設(shè)置屏幕由兩個選項(xiàng)卡組成:保護(hù)和限制器。單擊“保護(hù)”按鈕以訪問保護(hù)設(shè)置屏幕,或單擊菜單欄上的屏幕,然后單擊保護(hù)設(shè)置。
保護(hù)標(biāo)簽保護(hù)設(shè)置如圖5-14所示,并在以下段落中描述。
發(fā)電機(jī)過電壓-電壓電平(%)。該字段的值表示為標(biāo)稱發(fā)電機(jī)電壓,確定啟動發(fā)電機(jī)所需的發(fā)電機(jī)電壓水平過電壓條件。可在1中輸入100%至120%的過電壓百分比值
增量百分比。發(fā)電機(jī)過電壓狀態(tài)點(diǎn)亮前部的發(fā)電機(jī)過電壓LED面板
發(fā)電機(jī)過電壓——報(bào)警延時(秒)。此設(shè)置確定了發(fā)電機(jī)過電壓條件必須在DECS-100通知該條件之前存在。
Reactive Power Step Response - Decrement of VAR Setpoint (%). This field indicates the decrease that occurs to the FCR setpoint when the corresponding Decrement button is clicked. The "Decrease VAR Setpoint =" field is used to set and indicate the percentage that the var setpoint is decreased to when the Decrement button is clicked. Any setpoint value (expressed as a percent of nominal) within range or lower than the existing setpoint value can be typed into the "Decrease VAR Setpoint =" field. The var setpoint changes to the new value when the adjacent button is clicked. Clicking this button sends the var setpoint value to the DECS-100 and changes the color of the pushbutton from gray to red. Reactive Power Step Response - Meter Value. These fields and the dial pointer indicate the value of the selected var setpoint. When the var setpoint is changed by clicking the increment, decrement, or setpoint button, the meter value fields and dial pointer indicate the setpoint value. A new var setpoint, expressed as a kvar value or a percentage of nominal, can be typed directly into either Meter Value field or selected by dragging the dial pointer to the desired value. The new value is sent to the DECS-100 by clicking the Send button. Reactive Power Step Response - Current Setpoint (%). The active var setpoint (adjusted by using any of the previously mentioned methods) is displayed in this field. To return the var setpoint to the nominal setting, the button adjacent to the "VAR Setpoint (%) (Nominal)" field should be clicked. If the VAR tab is left to view other tabs or screens without returning the VAR setpoint to nominal, a var setpoint dialog box appears. Clicking the Yes button returns the var setpoint to nominal. Clicking No maintains the var setpoint at the current value. Protection Settings The Protection Settings screen consists of two tabs: Protection and Limiter. Click the Protection button to access the Protection Settings screen or click Screens on the menu bar and click Protection Settings. Protection Tab Protection settings are shown in Figure 5-14 and are described in the following paragraphs. Generator Overvoltage - Voltage Level (%). The value of this field is expressed as a percentage of the nominal generator voltage and determines the level of generator voltage required to initiate a generator overvoltage condition. An overvoltage percentage value of 100 to 120 percent may be entered in 1 percent increments. A generator overvoltage condition lights the Generator Overvoltage LED on the front panel. Generator Overvoltage – Alarm Time Delay (sec). This setting establishes the length of time that a generator overvoltage condition must exist before the DECS-100 annunciates the condition.