IS200AEPCH1BAA燃機(jī)電氣卡件
設(shè)置調(diào)整屏幕由兩個(gè)選項(xiàng)卡組成:設(shè)置點(diǎn)和啟動(dòng)。
設(shè)定點(diǎn)選項(xiàng)卡
設(shè)置調(diào)整屏幕的設(shè)置點(diǎn)選項(xiàng)卡設(shè)置如圖5-7所示
設(shè)定點(diǎn)選項(xiàng)卡在以下段落中描述。
自動(dòng)電壓調(diào)節(jié)器(AVR)-AVR設(shè)定點(diǎn)(V)。此設(shè)置字段用于輸入所需的發(fā)電機(jī)輸出端電壓。AVR設(shè)定值范圍取決于調(diào)節(jié)器感應(yīng)電壓和頻帶設(shè)置。
精細(xì)電壓調(diào)整-頻帶設(shè)置(%)。波段設(shè)置確定最小值和最大值允許對(duì)AVR設(shè)定點(diǎn)進(jìn)行調(diào)整(以調(diào)節(jié)器感應(yīng)電壓設(shè)置的百分比表示)(參見(jiàn)圖5-8))。頻帶設(shè)置值輸入為調(diào)節(jié)器感應(yīng)電壓設(shè)置的百分比以0.1%的增量在0至15%的范圍內(nèi)。
下降-設(shè)定點(diǎn)(%)。此設(shè)置控制DECS-100的無(wú)功下垂補(bǔ)償功能。
設(shè)定點(diǎn)值確定發(fā)電機(jī)電壓設(shè)定點(diǎn)中允許的變化量
DECS-100響應(yīng)無(wú)功負(fù)載。設(shè)定點(diǎn)值可從0%調(diào)整到10%,增量為0.01%. 設(shè)定點(diǎn)基于0.8功率因數(shù)負(fù)載。無(wú)功功率控制(VAR)-VAR設(shè)定點(diǎn)(額定值的%)。VAR設(shè)定值決定了在Var控制模式下運(yùn)行時(shí),DECS-100維持發(fā)電機(jī)Var。值從-100到+可以在VAR設(shè)定點(diǎn)字段中輸入100%,增量為1.0%。
功率因數(shù)控制(PF)-PF設(shè)定點(diǎn)。
PF設(shè)定點(diǎn)決定發(fā)電機(jī)功率因數(shù)的水平
在功率因數(shù)控制模式下運(yùn)行時(shí)由DECS-100維護(hù)。PF設(shè)定值為:可從-0.6調(diào)整至-1(1)或0.6至+1,增量為0.001。啟動(dòng)選項(xiàng)卡
設(shè)置調(diào)整屏幕的啟動(dòng)選項(xiàng)卡設(shè)置如圖5-8所示“啟動(dòng)”選項(xiàng)卡在以下段落中描述。
啟動(dòng)控制-發(fā)電機(jī)軟啟動(dòng)時(shí)間(秒)。該設(shè)置定義發(fā)電機(jī)軟啟動(dòng)的時(shí)間限制
電壓斜坡時(shí)間。軟啟動(dòng)時(shí)間將發(fā)電機(jī)電壓過(guò)沖降至最低,可設(shè)置為1至7200秒,以1秒為增量。
欠頻設(shè)置-轉(zhuǎn)角頻率(Hz)。轉(zhuǎn)角頻率設(shè)置定義了使DECS-100調(diào)整電壓設(shè)定點(diǎn)的頻率,以使發(fā)電機(jī)電壓如下:選定的伏特/赫茲斜率。在0.01中,可在此設(shè)置字段中輸入40至65赫茲的值增量。
欠頻設(shè)置-斜率(伏特/赫茲)。選擇發(fā)電機(jī)低頻保護(hù)的斜率
具有該每單位設(shè)置。可以以0.01的增量輸入0到3.00的坡度設(shè)置。
電壓匹配-速度(秒)。此設(shè)置決定發(fā)電機(jī)電壓的調(diào)整速度
DECS-100與總線電壓匹配。速度設(shè)置可在0.01內(nèi)從1秒調(diào)整到300秒增量。
電壓匹配-通過(guò)觸點(diǎn)禁用
此設(shè)置選擇用于禁用的DECS-100觸點(diǎn)輸入電壓匹配。選擇“52JK或52LM”允許52JK和52LM觸點(diǎn)輸入禁用電壓匹配。選擇“52JK”僅允許52JK觸點(diǎn)輸入禁用電壓匹配。
電壓匹配–模式。電壓匹配模式可以保持或恢復(fù)。何時(shí)維護(hù)選擇后,DECS-100設(shè)定點(diǎn)即使在發(fā)電機(jī)或公用事業(yè)之后仍保持在總線電壓水平斷路器打開(kāi)。當(dāng)選擇Revert(恢復(fù))時(shí),DECS-100設(shè)定點(diǎn)將恢復(fù)到其原始水平
發(fā)電機(jī)或公用設(shè)施斷路器斷開(kāi)。
Reactive Power Control (VAR) - VAR Setpoint (% of rated). The VAR Setpoint determines the level of generator vars maintained by the DECS-100 when operating in Var Control mode. Values from -100 to +100 percent in 1.0 percent increments may be entered in the VAR Setpoint field. Power Factor Control (PF) - PF Setpoint. The PF Setpoint determines the level of generator power factor maintained by the DECS-100 when operating in Power Factor Control mode. PF Setpoint values are adjustable from -0.6 to -1 (1) or 0.6 to +1 in 0.001 increments. Startup Tab The Startup-tab settings of the Setting Adjustment screen are shown in Figure 5-8. Each setting of the Startup tab is described in the following paragraphs. Startup Control - Gen Soft Start Time (sec). This setting defines the time limit for the generator soft-start voltage ramp time. The soft-start time minimizes generator voltage overshoot and can be set from 1 to 7,200 seconds in 1 second increments. Underfrequency Setting - Corner Frequency (Hz). The Corner Frequency setting defines the value of frequency that causes the DECS-100 to adjust the voltage setpoint so that the generator voltage follows the selected volts per hertz slope. A value of 40 to 65 hertz can be entered in this setting field in 0.01 increments. Underfrequency Setting - Slope (Volts/Hz). The slope for generator underfrequency protection is selected with this per-unit setting. A slope setting of 0 to 3.00 can be entered in increments of 0.01. Voltage Matching - Speed (sec). This setting determines how quickly the generator voltage is adjusted by the DECS-100 to match the bus voltage. The Speed setting is adjustable from 1 to 300 seconds in 0.01 increments. Voltage Matching – Disable by Contact. This setting selects the DECS-100 contact input used to disable voltage matching. Selecting “52JK or 52LM” allows either the 52JK or 52LM contact input to disable voltage matching. Selecting “52JK” allows only the 52JK contact input to disable voltage matching. Voltage Matching – Mode. The voltage matching mode can be Maintain or Revert. When Maintain is selected, the DECS-100 setpoint is maintained at the bus voltage level even after the generator or utility breaker opens. When Revert is selected, the DECS-100 setpoint reverts to its original level when the generator or utility breaker opens.