主營產(chǎn)品
PLC可編程控制器模塊,DCS卡件,ESD系統(tǒng)卡件,振動監(jiān)測系統(tǒng)卡件,汽輪機(jī)控制系統(tǒng)模塊,燃?xì)獍l(fā)電機(jī)備件等,優(yōu)勢品牌:Allen Bradley、BentlyNevada、ABB、Emerson Ovation、Honeywell DCS、Rockwell ICS Triplex、FOXBORO、Schneider PLC、GE Fanuc、Motorola、HIMA、TRICONEX、Prosoft等各種進(jìn)口工業(yè)零部件
產(chǎn)品廣泛應(yīng)用于冶金、石油天然氣、玻璃制造業(yè)、鋁業(yè)、石油化工、煤礦、造紙印刷、紡織印染、機(jī)械、電子制造、汽車制造、塑膠機(jī)械、電力、水利、水處理/環(huán)保、鍋爐供暖、能源、輸配電等等
ASSY 11993R2機(jī)器人模塊
干擾記錄器功能將受到一般限制記錄模擬變量,并由一般啟動或一般跳閘信號。二進(jìn)制信號狀態(tài)的變化仍然由事件記錄器記錄。因此,對于給定數(shù)量的信道和電力系統(tǒng)頻率,容量足以應(yīng)付540ms的10個事件每個的持續(xù)時間。文件PLOT.TXT陰謀。WinEVE、REVAL(用于評估干擾記錄器數(shù)據(jù)的程序)和Interface(數(shù)據(jù)轉(zhuǎn)換程序)的TXT用于測試集XS92a上的運(yùn)行干擾數(shù)據(jù))。
一般評論程序(WinEVE、REVAL和Interface)需要該文件陰謀。TXT能夠處理干擾記錄器數(shù)據(jù)。
對于接口,所有干擾記錄器數(shù)據(jù)Rexxx。xxx必須從字母RE開始。這些比率使WinEVE能夠確定次級
價值觀這些比率必須乘以主要c.t和v.t,以獲得主要系統(tǒng)值。接口不評估CO、TR和UN。
自動創(chuàng)建文件plotxxx.txt:文件plotxxx。txt自動保存在當(dāng)前目錄中保存時,操作員程序(HMI)從中啟動RE。316設(shè)置。plotxxx中的幾個文件。具有不同站號的txt(xxx)可以
可合并為單個plot.txt。文件繪圖。txt必須位于與REVAL的干擾記錄器數(shù)據(jù)位置相同評估方案。
安裝數(shù)據(jù)評估程序的說明
必須嚴(yán)格按照相關(guān)操作說明安裝數(shù)據(jù)評估程序。懷恩夫?qū)⑽募癙LOT.TXT”復(fù)制到以下目錄:C: \I650\事件調(diào)試過程中應(yīng)記錄干擾每個繼電器和存儲在上述目錄中的記錄。安裝樁號參數(shù)文件的步驟如下:
啟動WINEVE程序。
打開故障記錄
出現(xiàn)以下錯誤消息:C: \I650\車站\ST0xx.標(biāo)準(zhǔn)桿數(shù)找不到文件。
單擊確定。
選擇“參數(shù)”中的菜單項“導(dǎo)入工作站文件”菜單
選擇文件繪圖。TXT屬于該干擾記錄。在“參數(shù)”菜單中選擇菜單項“保存工作站”
The disturbance recorder function will thus be generally confined
to recording the analogue variables and be triggered by the
general start or general trip signals. Changes in the states of binary signals are nevertheless registered by the event recorder.It follows that for the given number of channels and power system frequency, the capacity is sufficient for 10 events of 540 ms
duration each.
File PLOT.TXT
PLOT.TXT for WinEVE, REVAL (programs for evaluating disturbance recorder data) and INTERFAC (data conversion program
for running disturbance data on the test set XS92a).
General remarks
The programs (WinEVE, REVAL and INTERFAC) need the file
PLOT.TXT to be able to process the disturbance recorder data.
For INTERFAC, all disturbance recorder data RExxxx.xxx must
start with the letters RE.These ratios enable WinEVE to determine the secondary
values. These ratios must be multiplied by the ratio of the
main c.t’s and v.t’s to obtain the primary system values.
INTERFAC does not evaluate CO, TR and UN.
Automatic creation of the file plotxxx.txt:
The file plotxxx.txt is automatically saved in the current directory
from which the operator program (HMI) was started when saving
the RE. 316 settings.
Several files plotxxx.txt with different station numbers (xxx) can
be combined to a single plot.txt. The file plot.txt must be at the
same location as the disturbance recorder data for the REVAL
evaluation program.Instructions for installing the data evaluation program
The data evaluation program must be installed in strict accordance with the relative operating instructions.
WINEVE
Copy the file “PLOT.TXT” to the directory:
C:\I650\EVENTS
A disturbance should be recorded during the commissioning of
every relay and the record stored in the directory given above.
The procedure for installing the station parameter files is as follows:
Start the WINEVE program.
Open a fault record
The following error message appears:
C:\I650\STATION\ST0xx.PAR
Could not find file.
Click on OK.
Select the menu item “Import station file” in the “Parameter”
menu.
Select the file PLOT.TXT belonging to this disturbance recording.
Select the menu item “Save station” in the “Parameter” menu