SLIMPAK 10923H5A自動化備件
未校準將顯示未校準的消息
對于從未使用過的新通道卡:校準。
應校準通道卡,并檢查其操作。
78校準過期將顯示校準過期信息
當預先配置的校準間隔已過期。
這是一條警告信息,表明傳感器:
應進行校準。一旦校準
已完成。消息將清除
如果需要,可以禁用此功能使用工程接口軟件配置程序。
77零信號過低
顯示零信號過低信息
校準期間,當傳感器為零時信號低于預先配置的電平,并且無法實現零校準。
對于催化傳感器,這通常是:表明兩者之間存在很大的不平衡傳感器的兩個檢測元件。
應檢查傳感器的安裝情況導線松動或更換傳感器。
對于mA傳感器,這通常意味著:傳感器的mA輸出需要:校準。
76零信號過高零信號過高信息為:當傳感器校準時顯示
零信號高于預先配置的電平并且不能實現零校準。
這是檢測其目標氣體和零氣體應適用于:傳感器?;蛘邔τ诖呋瘋鞲衅?,
這通常意味著存在較大的二者檢測不平衡
傳感器的元件
傳感器應檢查安裝是否有松動的電線或者更換傳感器。
對于mA傳感器,這通常意味著:
傳感器的mA輸出需要:校準。
75校準信號過低
校準信號過低信息為:當傳感器校準時顯示量程信號低于預配置值
液位和量程校準不能實現。這表明由于以下原因之一,傳感器過低:
a、 可能中毒的傳感器故障或損壞。
b、 校準氣體不正確。檢查校準氣瓶證書和年齡
c、 粘性氣體,如氯或氨沒有到達傳感器。
Uncalibrated
The uncalibrated message is displayed
for new channel cards that have never been
calibrated.
The channel card should be calibrated and
its operation checked.
78 Calibration Overdue
The calibration overdue message is displayed
when the pre-configured calibration interval
has expired.
This is a warning message that the sensor
is due for calibration. Once the calibration
has been completed the message will clear
If required, this function can be disabled
using the Engineering Interface Software
configuration program.
77 Zero Signal Too Low
The zero signal too low message is displayed
during calibration when the sensor zero
signal is below the pre-configured levels and
a zero calibration can not be achieved.
For catalytic sensors this would typically
signify there is a large imbalance between
the two detecting elements of the sensor.
The sensor installation should be checked
for loose wires or the sensor replaced.
For mA sensors this would typically signify
that the mA output from the sensor requires
calibrating.
76 Zero Signal Too High
The zero signal too high message is
displayed during calibration when the sensor
zero signal is above the pre-configured levels
and a zero calibration can not be achieved.
This is typical of the sensor detecting its
target gas and zero gas should be applied to
the sensor. Alternatively, for catalytic sensors,
this would typically signify there is a large
imbalance between the two detecting
elements of the sensor. The sensor
installation should be checked for loose wires
or the sensor replaced.
For mA sensors this would typically signify
that the mA output from the sensor requires
calibrating.
75 Calibration Signal Too Low
The calibration signal too low message is
displayed during calibration when the sensor
span signal is below the pre-configured
levels and a span calibration can not be
achieved.This indicates that the output from the
sensor is too low due to either:
a. a faulty sensor which may be poisoned
or damaged.
b. the calibration gas is incorrect. Check
the calibration gas bottle certificate and
age.
c. sticky gas such as chlorine or
ammonia is not reaching the sensor.