UR9EV繼電工控模塊
EEPROM故障。
EEPROM保存應(yīng)用程序配置數(shù)據(jù)。
顯示EEPROM故障消息如果存在校驗和差或無法執(zhí)行校驗和啟動期間的測試或定期自檢。
這是一個嚴重的卡故障,該卡需要更換。
Vps插件已安裝。
Vps插件用于設(shè)置Vps參考,不適用于操作傳感器。
Vps插件安裝信息為出廠信息
測試消息顯示時表明:傳感器上安裝了一個特殊模塊驅(qū)動模塊連接。
除非卡被錯誤地配備VP1模塊。這是嚴重的卡故障,因此需要更換。
94電流設(shè)置故障(僅催化)
當前設(shè)置故障信息為:如果通道卡未能:設(shè)置正確的催化傳感器橋啟動程序期間的電流。
檢查傳感器連接和電纜確保最大線路長度未超過阻抗。
93配置故障將顯示配置故障消息啟動期間,如果通道卡沒有配置信息或配置無效。
這是一個嚴重的卡故障,該卡需要更換。
92錯誤的插件顯示錯誤的插件消息在啟動期間,如果實際傳感器驅(qū)動安裝在通道卡上的模塊不同從通道卡中選擇的類型配置
應(yīng)檢查插件的與傳感器的兼容性,以及插件模塊或通道卡配置相應(yīng)地改變。
不適用高完整性繼電器故障。實際和要求的狀態(tài)高完整性繼電器輸出不匹配。
檢查高完整性繼電器卡是否:正確連接。如果可能,使用另一個已知工作高完整性繼電器或控制卡,以確定要更換的卡。硬件故障如果出現(xiàn)以下情況,將顯示硬件故障消息:
通道卡在其操作中檢測到故障或傳感器輸入故障。
檢查傳感器連接。刪除通道卡并將其插入兼容工作通道并檢查其運行情況
(ER86可能在此操作期間出現(xiàn)-此正常)。如果卡仍指示故障,則
必須更換。如果卡正在工作,則應(yīng)更換傳感器。
EEPROM Failure.
The EEPROM holds the application
configuration data.
The EEPROM failure message is displayed
if there is a checksum difference or it has
been impossible to carry out a checksum
test during start-up or periodic self test.
This is a serious card failure and, as such,
the card needs to be replaced.
Vps Plug-in Fitted.
The Vps plug-in is used to set the Vps
reference and is not suitable for operating
sensors.
The Vps plug-in fitted message is a factory
test message, when displayed indicates that
a special module is fitted to the sensor
drive module connections.
Unless the card has been incorrectly
supplied with a VP1 module fitted.This is a
serious card failure and, as such, the card
needs to be replaced.
94 Current Setting Fault (Catalytic Only)
The current setting fault message is
displayed if the channel card has failed to
set the correct catalytic sensor bridge
current during the startup routine.
Check the sensor connection and cable
line lengths to ensure that maximum line
impedance has not been exceeded.
93 Configuration Fault
The configuration fault message is displayed
during start-up if the channel card has no
configuration information or the configuration
is not valid.
This is a serious card failure and, as such,
the card needs to be replaced.
92 Wrong Plug-in
The wrong plug-in message is displayed
during start-up if the actual sensor drive
module fitted to the channel card is different
from the type selected in the channel card
configuration.
The plug-in should be checked for
compatibility with the sensor and either the
plug-in module or channel card configuration
changed accordingly.
Not applicable
High Integrity Relay Fault.
The actual and demanding states of the
high integrity relay outputs do not match.
Check that the high integrity relay card is
properly connected. If possible use another
known working high integrity relay or control
card to determine which card to replace.Hardware Fault
The hardware fault message is displayed if
the channel card detects a fault in its operation
or a fault with a sensor input.
Check the sensor connections. Remove the
channel card and insert it into a compatible
working channel and check its operation
(ER86 may appear during this operation - this
is normal). If the card still indicates a fault, it
must be replaced. If the card is working, the
sensor should be replaced.