一旦設置了臨時IP地址,就可以使用以太網接口通過網絡訪問(例如通過機器版編程軟件)。然后應使用編程器配置正確的IP地址用于以太網接口。
默認IP地址(0.0.0.0)嘗試通過設置IP地址BOOTP默認IP地址值(0.0.0.0),無論是從硬件配置還是備份配置,使以太網接口請求臨時IP來自網絡上BOOTP服務器設備的地址。報告重復IP地址PACSystems RX7i不會在控制器故障中記錄異常或故障表,當它在網絡上檢測到重復的IP地址時。
EMG ECU01.5操作顯示屏多零周期EGD交易所可能不會產生類似的結果樣本數量如果在生產期內配置了多個EGD生產的交易所零,交易所可能不會產生類似數量的樣本。由于道路當多個交換“以最快的速度”進行調度時,就會出現這種調度可能,“一些零周期交換可能會產生更多的樣本比其他人。為了獲得更一致的EGD生產,請配置生產的EGD與非零生產期的交換。SRTP時更改IP地址連接打開可能會生成日志事件與遠程SRTP客戶端建立的開放SRTP服務器連接不是當RX7i的IP地址更改時(通常通過存儲RX7i的新硬件配置)。90系列SRTP客戶端(“SRTP通道”)報告9690H或0190H狀態;SRTP連接可能保持打開狀態直到連接因客戶端超時而終止。90-70系列數據報不是支持不支持90-70系列數據報。這意味著90-70系列-格式來自主機通信工具包應用程序的變量列表請求將失敗。(90-30系列-支持格式化數據報,但無法訪問中的%P或%L內存RX7i.)
AUP參數不應為改變高級用戶參數“wsnd\u buf”不應由用戶更改。更改此參數的值可能會導致LAN LED熄滅,并且用于斷開連接的以太網接口。重載會阻塞車站
如PACSystems Station Manager的TCP/IP通信中所述手動,GFK-2225,第1章,重型EGD和/或SRTP負載可阻塞電站管理器操作。
Once a temporary IP address has been set up, the Ethernet Interface can be
accessed over the network (such as by the Machine Edition programming
software). The programmer should then be used to configure the proper IP address
for the Ethernet Interface.
Default IP address (0.0.0.0)
attempts to set IP address via
BOOTP
The default IP address value (0.0.0.0), whether obtained from HW Configuration or
backup configuration, causes the Ethernet Interface to request a temporary IP
address from a BOOTP server device on the network.
Reporting of duplicate IP address The PACSystems RX7i does not log an exception or a fault in the Controller Fault
Table when it detects a duplicate IP address on the network.
Multiple zero period EGD
exchanges may not produce similar
numbers of samples
If more than one EGD produced exchange is configured for a production period of
zero, the exchanges may not produce similar numbers of samples. Due to the way
that scheduling occurs when multiple exchanges are scheduled “as fast as
possible,” some zero period exchanges may produce significantly more samples
than others. For more consistent EGD production, configure the produced EGD
exchanges with non-zero production periods.
Changing IP address while SRTP
connection open may generate log
events
Open SRTP Server connections established with a remote SRTP client are not
terminated as expected when the RX7i’s IP address is changed (typically by storing
a new HW Configuration to the RX7i). A Series 90 SRTP client (“SRTP channels”)
reports either a 9690H or 0190H status; the SRTP connection may remain open
until the connection is terminated as a result of a client timeout.
Series 90-70 datagrams are not
supported
Series 90-70 datagrams are not supported. This means that Series 90-70 - format
variable list requests from Host Comm Toolkit applications will fail. (Series 90-30 –
format datagrams are supported, but cannot access %P or %L memory in the
RX7i.)
AUP parameter should not be
changed
The Advanced User Parameter “wsnd_buf” should not be changed by the user.
Changing the value of this parameter may cause the LAN LED to go out and the
Ethernet Interface to drop connection.
Heavy load can block station
manager
As explained in TCP/IP Communications for PACSystems Station Manager
Manual, GFK-2225, Chapter 1, a heavy EGD and/or SRTP load can block Station
Manager operation.