Specific instructions must be followed when installing a memory backup
battery. For more information, refer to the PACSystems Controller
Battery and Energy Pack Manual, GFK-2741.
CPU might not detect low-battery condition Unless a smart battery is in use, PACSystems CPUs may not detect a
low-battery condition early enough to provide a meaningful warning to
the user to replace the battery. A legacy battery with very low capacity
may still have a terminal voltage high enough to report that it is a good
battery. In this case, when the battery starts supplying the memory
power (battery backup), the battery voltage would quickly drop to
unacceptable levels, with little warning to the user before failure.
To insure against data loss when using any type of battery other than a
smart battery, users should replace batteries in accordance with the
guidelines provided in PACSystems Controller Battery and Energy Pack
Manual, GFK-2741. Additionally, users could save logic and hardware
configuration to flash.
Ethernet disconnect during word for word
change
If the Ethernet connection is broken during a word-for-word change, the
programmer may not allow a subsequent word-for-word change after
reconnecting due to the fact that it thinks another programmer is
currently attached. If this occurs, you should go offline and then back
online again.
VME modules operating as VME masters are
not supported
The RX7i does not support VME modules operating as bus masters.
Store of hardware configuration with
multiple GBCs
Storing a hardware configuration containing two or more Series 90-70
GBCs twice may cause one GBC to fail configuration. Clearing the
hardware configuration between stores will prevent this fault from being
generated. (Note: This issue does not affect Series 90-30 GBCs.)
Simultaneous Clears, Loads and Stores not
supported
Currently, the RX7i does not support multiple programmers changing
CPU contents at the same time. The programming software may
generate an error during the operation.