TRICONEX 3000520-390C1R端子板,3000520-390C1R英文說明
用于編程器或HMI/SCADA的所有以太網接口(IC693CMM321)模塊與該CPU的通信必須是以下修訂組之一:IC693CMM321-CC或更高版本IC693CMM321-AA或-BA升級至固件版本1.11或更高版本?CPU363型號不支持通信配置(SNP從站除外通過電源端口),使用手持式編程器(HHP)。?此版本的CPU需要IC693BEM340 FIP總線控制器固件版本3.00或更高版本固件。此硬件版本解決的問題原始緩存RAM組件已過時,不再可用。
TRICONEX 3000520-390C1R端子板新組件是最低的電源部分當前可用。此固件版本解決的問題CPU350、CPU360或CPU363 PLC中IC693ALG222/223模塊故障的丟失/添加在所有以前的CPU固件版本中,當兩個或更多高密度模擬輸入模塊(IC693ALG222)時或IC693ALG223)安裝在CPU機架中,模塊中的所有16個輸入通道都處于活動狀態,丟失當CPU機架處于工作狀態時,可能會出現模塊故障,并為其中一個模擬模塊增加模塊故障已通電。版本10.74中更正了此問題。時間問題IC693ALG220/221-F或更早版本模塊可能導致錯誤%CPU讀取的AI值IC693ALG220/221-F或早期模塊版本報告的%AI值可能不正確并表現出不穩定的行為。某些電流或電壓水平在應用于模塊的輸入范圍內,可能會導致%AI值報告不正確。問題源于使用特定的光耦合器,這些光耦合器可能會在CPU 35x/36x模塊中出現計時問題。IC693ALG220/221-G及更高版本的模塊不會出現此問題
All Ethernet Interface (IC693CMM321) modules used for programmer or HMI/SCADA
communications with this CPU must be one of the following revision groups:
IC693CMM321-CC or later
IC693CMM321-AA or -BA upgraded to firmware version 1.11 or later
? The CPU363 model does not support configuration of communications (other than SNP Slave
through the power supply port) using the Hand-Held Programmer (HHP).
? IC693BEM340 FIP Bus Controller firmware version 3.00 or later is required for this release of CPU
firmware.Problems Resolved by this Hardware Revision
The original cache RAM component is obsolete and no longer available. The new component is the lowest
power part currently available.
Problems Resolved by this Firmware Revision
Loss/add of module faults with IC693ALG222/223 modules in CPU350, CPU360 or CPU363 PLC
In all previous CPU firmware versions, when two or more high-density analog input modules (IC693ALG222
or IC693ALG223) are installed in the CPU rack, and all 16 input channels are active in the modules, loss of
module and addition of module faults for one of the analog modules may occur when the CPU rack is
powered on. This issue is corrected in version 10.74.Timing Issue with
IC693ALG220/221-F or earlier
modules may result in incorrect
%AI values read by CPU
The %AI values reported by an IC693ALG220/221-F or earlier module revision
may be incorrect and exhibit erratic behavior. Certain current or voltage levels
within the input range applied to the module can cause the %AI values to be
reported incorrectly. The problem stems from the use of particular optocouplers that may exhibit timing issues with CPU 35x/36x modules.