TRICONEX 9662-610模擬量端子板,9662-610中文使用說(shuō)明
AAUI(收發(fā)器)端口14針AAUI端口通過(guò)IEEE 802.3連接到外部以太網(wǎng)兼容收發(fā)器收發(fā)器電纜。GE Fanuc目錄號(hào)IC649AEA102(用于10Base T)或IC649AEA103(用于10Base2)是合適的收發(fā)器(詳見(jiàn)附錄J)。默認(rèn)MAC地址標(biāo)簽?zāi)J(rèn)MAC地址標(biāo)簽列出了該模塊要使用的以太網(wǎng)MAC地址。序列號(hào)標(biāo)簽序列號(hào)標(biāo)簽表示該接口的序列號(hào)。
TRICONEX 9662-610模擬量端子板以太網(wǎng)接口模塊文檔有關(guān)詳細(xì)信息,請(qǐng)參閱GFK-1541,Series 90-30 TCP/IP Ethernet Communications User’s Manual(GFK-1541,Series 90-30 TCP/IP以太網(wǎng)通信用戶手冊(cè))。此硬件版本使用當(dāng)前可用的組件替換過(guò)時(shí)的緩存RAM。在在室溫下,新部件將電池壽命從6年縮短到10個(gè)月。固件版本10.74是一個(gè)維護(hù)版本,包括“問(wèn)題”中描述的更改通過(guò)第2頁(yè)的“此固件版本解決”。升級(jí)此硬件版本不需要或不可用現(xiàn)場(chǎng)升級(jí)。功能兼容性?使用原始緩存RAM組件,電池壽命為6年25°C,在60°C時(shí)為1?年。當(dāng)前可用部件上的數(shù)據(jù)保留電流將電池壽命降低到10個(gè)月25°C和60°C下5個(gè)半月。?機(jī)器版PLC Logic Developer 2.11或更高版本,或VersaPro 2.02或更高版本應(yīng)用于配置和編程這些CPU模型。?C編程必須使用4.00或更高版本的C工具包。
AAUI (Transceiver) Port
The 14-pin AAUI port connects to an external Ethernet-compatible transceiver via an IEEE 802.3
transceiver cable. GE Fanuc catalog number IC649AEA102 (for 10Base T) or IC649AEA103 (for
10Base2) are suitable transceivers (see Appendix J for details).
Default MAC Address Label
The Default MAC Address label lists the Ethernet MAC address to be used by this module.
Serial Number Label
The Serial Number Label indicates the serial number of this Interface.
Ethernet Interface Module Documentation
For details, refer to GFK-1541, Series 90-30 TCP/IP Ethernet Communications User’s Manual.This hardware revision replaces an obsolete cache RAM with a component that is currently available. At
room temperature, the new part reduces the battery life from 6 years to 10 months.
Firmware version 10.74 is a maintenance release that consists of the changes described in “Problems
Resolved by this Firmware Revision” on page 2.
Upgrades
No field upgrade is required or available for this hardware revision.Functional Compatibility
? With the original cache RAM component, the battery life was 6 years 25°C and 1? years at 60°C.
The data retention current on the currently available part reduces the battery life to 10 months at
25°C and 5? months at 60°C.
? Machine Edition PLC Logic Developer version 2.11 or later, or VersaPro version 2.02 or later should
be used to configure and program these CPU models.
? Version 4.00 or later of the C toolkit must be used for C programming.