HONEYWERLL 51309288-275工控模塊,51309288-275說(shuō)明書在線閱讀
制作100%屏蔽電纜使用以下步驟構(gòu)建100%屏蔽電纜:1.從定制電纜上剝?nèi)ゼs5/8英寸的絕緣層,露出盾2.從任何直接插入舊型號(hào)的連接器上取下公針腳1遠(yuǎn)程基板(IC693CHS393E、IC693CHS399D或更早版本)。3、將開口環(huán)套圈置于電纜絕緣層上(圖10-17)。4、將屏蔽層折疊回電纜絕緣層和套圈頂部。5.將金屬罩的凸緣放在折疊護(hù)罩的頂部,并牢固夾緊引擎蓋。6.測(cè)試電纜在兩個(gè)連接器外殼之間的導(dǎo)通性。連接歐姆表在外殼之間,彎曲電纜兩端。
HONEYWERLL 51309288-275工控模塊
如果金屬化連接器罩如果未與兩端的電纜屏蔽層正確接觸,則連接將在歐姆表上顯示間歇性連續(xù)性。7.將金屬罩電纜插入遠(yuǎn)程基板擴(kuò)展端口連接器或插入GE Fanuc Y形電纜,并牢固擰緊兩個(gè)螺釘。安裝和擰緊螺釘將屏蔽與遠(yuǎn)程基板進(jìn)行電氣連接機(jī)架接地,其應(yīng)依次連接至接地在“安裝”一章的“基板安全”標(biāo)題下進(jìn)行說(shuō)明接地電路圖以下接線圖顯示了輸入/輸出擴(kuò)展系統(tǒng)的接線配置電纜。提供了點(diǎn)到點(diǎn)電纜和Y形電纜的接線圖。在遠(yuǎn)程基板IC693CHS393E(及更早版本)和IC693CHS399D(及更早版本)中,它是需要拆下電纜插入基板處的配套電纜的針腳1。這意味著當(dāng)使用工廠制造的Y形電纜IC693CBL300時(shí),必須斷開插腳1從公端拔出,插入遠(yuǎn)程基板,然后與一起使用這些基板之一。這些基板的定制Y形電纜應(yīng)使用
Making a 100% Shielded Cable
Use the following steps to build a 100% shielded cable:
1. Strip approximately 5/8 inch of insulation from your custom cable to expose the
shield.
2. Remove the male Pin 1 from any connector plugging directly into an older version
remote baseplate (IC693CHS393E, IC693CHS399D, or earlier).
3. Put split-ring ferrule over cable insulation (Figure 10-17).
4. Fold the shield back over top of the cable insulation and ferrule.
5. Place the collar of the metal hood over top of the folded shield and securely clamp
the hood.
6. Test your cable for continuity between both connector shells. Connect an ohmmeter
between the shells and flex the cable at both ends. If the metalized connector hood
is not making proper contact with the cable shield at either end, the connection will
show intermittent continuity on the ohmmeter.
7. Plug the metal hooded cable onto a remote baseplate expansion port connector or
into a GE Fanuc WYE cable and securely tighten the two screws. Installing and
tightening the screws will electrically connect the shield to the remote baseplate
frame ground, which should in turn should be connected to earth ground as
instructed in the “Installation” chapter, under the heading “Baseplate Safety
GroundingWiring Diagrams
The following wiring diagrams show the wiring configuration for I/O expansion system
cables. Wiring diagrams are provided for both point-to-point cables and Wye cables.In remote baseplates, IC693CHS393E (and earlier) and IC693CHS399D (and earlier), it is
necessary to remove pin 1 of the mating cable where the cable plugs into the baseplate.