P0973JM交換機(jī)模塊最大負(fù)載/當(dāng)前偏移對于連接到腹板張力電子裝置PFEA113的每個(gè)稱重傳感器,最大負(fù)載范圍為±6.5 x Fnom的存儲(chǔ)器將存儲(chǔ)施加到稱重傳感器的最高負(fù)載。最大負(fù)載包括:?稱重傳感器零信號(hào)(稱重傳感器上無負(fù)載)?FRT,稱重傳感器測量方向上皮重的作用力分量和?FR,測得的力(在測量方向上的張力力分量)稱重傳感器)如果更換稱重傳感器,則可以重置最大負(fù)載內(nèi)存。可以將模擬設(shè)置為打開或關(guān)閉。如果模擬設(shè)置為開啟,參數(shù)PercentofNoma和PercentofNomb將為顯示。如果在ObjectType和中選擇了單側(cè)A,則不會(huì)顯示百分比OFNOMB如果在ObjectType中選擇了單側(cè)B,則不會(huì)顯示節(jié)點(diǎn)百分比。參數(shù)percentofnom可以一步一步地設(shè)置在-100和+200之間。什么時(shí)候simulation設(shè)置為ON,它將替換稱重傳感器的測量值。值+100表示該值與加載到Fnom的稱重傳感器相同。激活模擬時(shí)不能使用零集。當(dāng)模擬設(shè)置為打開時(shí),紅色狀態(tài)led點(diǎn)亮,顯示屏上顯示消息“Simulation”。如果按下“ok”(確定),則消息以與故障和警告相同的方式移動(dòng)到操作員菜單的底部信息。SetFactory Default將模擬設(shè)置為關(guān)閉。當(dāng)“模擬”設(shè)置為“開”時(shí),默認(rèn)值為:–正常百分比=55%–NOMB百分比=45%Only menus for connected load cells are shown.The service menu has parameters that can be viewed (displayed) only and parameters that canbe set.? Parameters that can be viewed only:– Version: XX.X
Displays PFEA113 software version.– MaximumLoad A, MaximumLoad B, MaximumLoad C, MaximumLoad D
Displays maximum load (for connected load cells) since last reset.PresentOffset A, PresentOffset B, PresentOffset C, PresentOffset DDisplays zero offset (for connected load cells) at last zero set.Maximum Load / Present Offset
For each load cell connected to the web tension electronics PFEA113, a maximum load
memory, with the range ±6.5 x Fnom, will store the highest load that is applied to the load cell.
The maximum load consists of:? load cell zero signal (with no load on the load cell)
? FRT, applied force component of tare in the measuring direction of the load celland
? FR, measured force (force component of tension in the measuring direction of
the load cell)The maximum load memory can be reset if a load cell is replacedSimulation can be set to ON or OFF.
If simulation is set to ON, the parameters PercentOfFnomA and PercentOfFnomB will be
displayed. PercentOfFnomB is not shown if Single side A has been selected in ObjectType and
PercentOfFnomA is not shown if Single side B has been selected in ObjectType.
The parameter PercentOfFnom can be set between –100 and +200 in steps of one. When
simulation is set to ON, it replaces the measured value from the load cells. The value +100
means that the value is the same as load cell loaded to Fnom.
Zero set can not be used when simulation is activated. When simulation is set to ON, the red
status led is lit and on the display the message “Simulation” is shown. If “ok” is pressed, the
message is moved to the bottom of the Operator menu in the same way as failure and warning
messages.
SetFactory Default sets the simulation to OFF.
When simulation is set to ON, the default values are:
– PercentOfFnomA = 55%
– PercentOfFnomB = 45%