Operating Requirements
1. Avoid situations where all of the following are true at the same time:
- the GNIU's Enhanced Diagnostics Mode is set to Enabled
- the GNIU is online with a Genius Bus Controller.
- serial communications (programmer operations: download remote
I/O configuration, verify equality, clear configuration; or Winloader)
are taking place.
Disconnect the GNIU from the Genius bus before attempting any
serial communications if a hardware configuration with Enhanced
Diagnostics Mode set to Enabled either is currently installed or will
be installed in the GNIU.
After completing serial communications disconnect the serial cable
from the GNIU’s expansion port. The GNIU can then be reattached
to the Genius bus.
An alternative to disconnecting the GNIU from the Genius bus is to
power off or disconnect all of the Genius Bus Controllers on the bus.
2. Forcing an I/O point on the GNIU is not permitted.
3. In Enhanced Diagnostics mode, the GNIU continually runs extensive
diagnostic tests in the background during normal operation. These
diagnostics cause the GNIU to be more sensitive to disturbances
on the Genius bus. When a Genius bus disturbance or
spontaneous hardware failure causes a diagnostic test to declare
an error, the GNIU stops communicating on the Genius bus and
attempts to reset itself. The loss of communications causes the
host PLC(s) to log a Loss of Device fault and default the affected
inputs (according to the host’s configuration). GMR PLCs will
disregard the channels associated with that GNIU. If the GNIU is
able to revive itself, it tries to resume normal operation several
seconds later. If this is successful, the host PLC(s) will log an