WOODWARD 8444-1067數(shù)字調(diào)速器,8444-1067如何使用
使用附加配置文件
該程序使用RSLogix 5000的15.00、16.03和17.00版本進行了測試。
配置模塊時,請確保CLX處于程序模式。
從SST背板通信模塊產(chǎn)品CD中,運行SST Profibus進入產(chǎn)品菜單/SST-PB3-CLX-RLL安裝背板產(chǎn)品。這將
安裝以下組件以配置AOP模塊:o SST Profibus配置工具
o固件模塊Pfbclx。ss4和pfbclx。默認(rèn)安裝目錄為Program
WOODWARD 8444-1067數(shù)字調(diào)速器o RSLogix 5000 AOP示例梯形圖代碼。默認(rèn)安裝目錄為ProgramControlLogix\AOP
2、從SST背板通信模塊產(chǎn)品CD中,選擇產(chǎn)品菜單/SST SST-PB3-CLX-RLL并運行羅克韋爾的RSLogix 5000 AOP安裝,然后按照說明書
AOP要求SST-PB3-CLX-RLL加載固件模塊Pbfclx。ss4 v8.6或更高和Pfbclx。ss3 7.26或更高版本。pfbclx的版本。ss4在通電時顯示。
確定pfbclx的版本。ss3,執(zhí)行中的命令字符串“ver pfbclx.ss3”超級終端。確定pfbclx的版本。ss3或如果您需要升級
固件模塊請參閱第8章“升級掃描儀固件”一節(jié)。筆記
升級模塊固件以支持AOP后,Profibus ID數(shù)字將從0x0876更改為0x0C44。此新ID影響模塊作為DP從機。如果需要,可以強制模塊繼續(xù)使用
Profibus ID 0x0876,啟用名為Legacy\u ID\u 0876的選項在中配置其加載項配置文件時的模塊配置選項卡
RSLogix 5000。
Using the Add-on-Profiles
This procedure was tested with versions 15.00, 16.03 and 17.00 of RSLogix 5000.
Note
When you are configuring the Module, ensure that the CLX is in
Program mode.
1.
From the SST Backplane Communication Module Products CD, run the SST Profibus
backplane Products installation by going to Product Menu/SST-PB3-CLX-RLL. This will
install the following components to configure the module for AOP:
o
SST Profibus Configuration Tool
o
Firmware modules Pfbclx.ss4 and pfbclx.ss3. Default install directory is Program
Files\BradCommunications\SST Profibus\Firmware
o
RSLogix 5000 AOP sample ladder code. Default install directory is Program
Files\BradCommunications\SST Profibus\Ladder Sample Codes for
ControlLogix\AOP
2.
From the SST Backplane Communication Module Products CD, select Product Menu/ SST
SST-PB3-CLX-RLL and run Rockwell’s RSLogix 5000 AOP install and follow the
instructions.
3.
AOP requires the SST-PB3-CLX-RLL to be loaded with firmware modules Pbfclx.ss4 v8.6
or higher and Pfbclx.ss3 7.26 or higher. The version of pfbclx.ss4 is displayed at power-up.
To determine the version of pfbclx.ss3, execute the command string “ver pfbclx.ss3” in
HyperTerminal. To determine the version of pfbclx.ss3 or if you need to upgrade the
firmware modules see chapter 8, section Upgrading the Scanner Firmware.
Note
After upgrading firmware on module to support AOP, the Profibus ID
number will change from 0x0876 to 0x0C44. This new ID affects the
module as a DP Slave. If needed, you can force the module to still use
Profibus ID 0x0876 by enabling the option called Legacy_ID_0876 on
the Module Configuration tab when you configure its Add-on-Profile in
RSLogix 5000.