8-Point Supervised Digital
Output Modules
Designed for the most critical applica
tions, Supervised Digital Output (SDO)
modules meet the needs of systems
whose outputs remain in a single state
for extended periods of time (in some
applications, for years). An SDO
module receives output signals from
the Main Processors on each of three
channels. Each set of three signals is
then voted upon by a fully fault-tolerant
quadruplicated output switch whose
elements are mechanical power relays,
so that one voted output signal is passed
to the field termination.
Each SDO module has voltage and
current loopback circuitry coupled with
? A shorted load in the de-energized
state
Failure to detect field voltage on any
output point energizes the power alarm
indicator. Failure to detect the presence
of a load energizes the load alarm indi
cator. When an optional secondary
power supply is used, shorted loads in
the Off state can be detected. (This
feature is not provided on Model
3611E, an AC module.)
All SDO modules support hot-spare
capability, and they require separate
external termination panels (ETP) with
a cable interface to the Tricon back
plane.
sophisticated online diagnostics that
verify the operation of each output
switch, the field circuit and the pres
ence of a load. This design provides
complete fault coverage without the
need to influence the output signal.
The modules are called “supervised”
because fault coverage is extended to
include potential field problems. In
other words, the field circuit is super
vised by the SDO module so that the
following field faults can be detected:
? Loss of power or blown fuse
? Open or missing load
? A field short resulting in the load
being energized in error