Please retain this information with your Bus Controller User’s Manual (GFK-1038A). A
user manual is not shipped with the bus controller. User manuals can be ordered
separately. They are also included in the document library on CD-ROM.
Capacities and Performance of this Release of the FIP Bus Controller
The information that follows provides a known benchmark for future regression testing.
It also can be used to estimate the performance of a planned system.
This information is from actual measurements taken on a fully operational PLC and FIP
network. The I/O data consisted of state TVAs only. Validator TVAs were not configured
for exchange on the network. To achieve the best possible network performance, the
elimination of validator TVAs is recommended.
Example 1
In this example, two PLCs (PLC1 and PLC2) are connected to a FIP network as shown
below. PLC1 and PLC2 are configured with 4 synchronous scan sets at periods of 20ms,
40ms, 80ms, and 160ms. The logic of the sync programs in PLC1 increments a value and
sends it to the corresponding sync program in PLC2. The logic of each sync program in
PLC2 simply echoes the data it receives.