HONEYWELL FC-PSU-UNI2450U V2.1機器人模塊, FC-PSU-UNI2450U V2.1說明書文檔
某些總線狀況可能會影響網絡輸入/輸出
事件,如冗余總線的同時切換、部分總線斷開(其中一個
雙絞線)或其他總線在潛在仲裁器上斷開可能會導致網絡。
無法通過TCP/IP存儲硬件配置
無法通過FIP TCP/IP成功存儲硬件配置
FC-PSU-UNI2450U V2.1
未設置通用輸入數據的點故障觸點
當無法成功使用通用設備的COMV時,點故障
未設置通用輸入數據的聯系人。他們總是很清楚。但是,如果
生成通用數據的設備丟失,用戶故障觸點設置正確。
Ping 3000字節或更多的消息可能會導致FBC掛起
如果向FBC發送3000字節或更多的Ping消息,可能會導致掛起或
HONEYWELL FC-PSU-UNI2450U V2.1機器人模塊
使FBC模塊崩潰。
Certain Bus Conditions May Affect Network I/O
Events such as simultaneous switching of redundant busses, partial bus breaks (one of
twisted pair), or a different bus broken on potential arbiters may cause glitches of I/O on
the network.
Hardware Configuration Cannot Be Stored via TCP/IP
The hardware configuration cannot be successfully stored through a FIP TCP/IP
connection.
Point Fault Contacts For Generic Input Data Are Not Set
When a COMV from a generic device cannot be consumed successfully, the point fault
contacts for the generic input data are not set. They are always clear. However, if the
device that produces the generic data is lost, the subscriber fault contact is correctly set.
Ping Messages of 3000 Bytes or More May Cause the FBC to Hang
If a Ping message of 3000 bytes or more is sent to the FBC, it may result in hanging or
crashing the FBC module.